DemirDöküm Burners

GAS Series Proportional Burners

Central Systems

Superior Features

Maximum Fuel Saving

Burner models with single grade, double grade, and proportional modulation mix air and fuel in optimum proportions and provide fuel saving.

Low Sound Level

Thanks to their special design, DemirDöküm burners operate at a very low sound level without requiring burner silencers.

Easy Maintenance

All components on burners provide reach to combustion head without disassembling the burner thanks to the sliding mechanism during service.

Specifications

Specifications

GAS 9 PMGAS 10 PM
General Properties
Double grade operationYesYes
Operation with ModulationYesYes
FuelNatural GasNatural Gas
Capacity
Capacity 2nd gradekW1.744 - 3.4882.441 - 4.885
Capacity 2nd gradeMcal/h1.500 - 3.0002.100 - 4.200
Capacity 1st gradekW8701.140
Capacity 1st gradeMcal/h750990
Efficiency
Net thermal valueMcal/Nm38,6 - 7,48,6 - 7,4
Net thermal valuekWh/Nm310 - 8,610 - 8,6
Absolute densitykg/Nm30,71 - 0,780,71 - 0,78
Max. CapacityNm3/h348 - 406488 - 588
Pressure at max. efficiencymbar13,4 - 19,821 - 31
Electrical Properties
Electric sourceV230 - 400 neutralized ~+ / - 10 %230 - 400 neutralized ~+ / - 10 %
Electric sourceHz50 - three phase50 - three phase
Electric motorrpm2.9002.900
Electric motorV220 - 240 - 380 - 415220 - 240 - 380 - 415
Electric motorA31,7 - 18,350,2 - 29,5
Ignition transformatorV1 -V2230 V - 1 x 15 kV230 V - 1 x 15 kV
Ignition transformatorI1 -I21 A - 25 mA1 A - 25 mA
Electric power consumptionW maks12.00017.000
Electric protection levelIP 40IP 40
Other
OperationInterrupted (Minimum 1 stops within every 24 hours) , Two-Grade (Low or high flame) and single-grade (all - none)Interrupted (Minimum 1 stops within every 24 hours) , Two-Grade (Low or high flame) and single-grade (all - none)
Standard ImplementationBoilers: Water, Vapor, Hot OilBoilers: Water, Vapor, Hot Oil
Environment temperature°C0 - 400 - 40
Combustion air temperature°C maks6060

Downloads

Downloads